Voltage Drop Calculator — Free Online Electrical Tool
Calculate voltage drop across electrical conductors based on wire gauge, length, current draw, and material to ensure your installation meets NEC recommendations.
Voltage Drop Results
5.29% drop
Supply Voltage
120.0 V
Receiving End
113.65 V
Formula
V_drop = (2 x L x I x R) / CML = 100 ft, I = 20 A, Gauge = 12 AWG (copper)
Warning: 5.29% exceeds the NEC recommended 3% maximum. Consider using a larger wire gauge or shorter run.
Wire Gauge Reference Table
| AWG Gauge | Circular Mils | Max Amps (Cu) | Max 3% Run @120V/20A (Cu) | Typical Use |
|---|---|---|---|---|
| 14 AWG | 4,107 | 15A | 30 ft | 15A lighting circuits |
| 12 AWG | 6,530 | 20A | 47 ft | 20A general purpose |
| 10 AWG | 10,380 | 30A | 75 ft | 30A dryers, water heaters |
| 8 AWG | 16,510 | 40A | 119 ft | 40A ranges, large appliances |
| 6 AWG | 26,240 | 55A | 189 ft | Sub-panels, large equipment |
| 4 AWG | 41,740 | 70A | 301 ft | Feeder circuits, sub-panels |
| 2 AWG | 66,360 | 95A | 479 ft | Service entrance, large feeders |
| 1/0 AWG | 105,600 | 125A | 762 ft | Main service entrance |
Related Calculators
Ohms Law Calculator
Calculate voltage, current, resistance, and power using Ohm's law.
Resistor Calculator
Decode resistor color bands and calculate series/parallel resistance.
Horsepower Calculator
Calculate horsepower from torque and RPM or convert between units.
Half-Life Calculator
Calculate radioactive decay, remaining amounts, and decay constants.
Percentage Calculator
Calculate percentages, percentage changes, and proportional values.
Unit Converter
Convert between different measurement units for length, weight, and more.
About this calculator
Voltage Drop Formula
Single-Phase Voltage Drop
V_drop = (2 x L x I x R) / CM Percentage Voltage Drop
%V_drop = (V_drop / V_supply) x 100 Three-Phase Voltage Drop
V_drop = (1.732 x L x I x R) / CM Variables Explained
- V_drop: The voltage lost across the wire conductors, measured in volts. This is the difference between the supply voltage at the panel and the voltage delivered to the load at the far end of the circuit.
- L: One-way wire length in feet. The factor of 2 in the formula accounts for both the supply conductor and the return conductor, since current must flow through both.
- I: Current flowing through the circuit in amperes. Higher current produces proportionally more voltage drop because the power lost as heat in the conductor equals I-squared times R.
- R: Resistivity of the conductor material in ohm-circular mils per foot. Copper has a resistivity of 10.37 and aluminum has 17.02 at 75 degrees Celsius, the standard operating temperature assumed by the NEC.
- CM: Circular mil area of the wire gauge. This is the cross-sectional area of the conductor; larger values mean less resistance and less voltage drop per unit length.
Step-by-Step Example
Calculate the voltage drop for a 20A load on a 120V circuit using 12 AWG copper wire with a 100-foot run:
- Identify values: L = 100 ft, I = 20 A, R = 10.37 (copper), CM = 6,530 (12 AWG)
- Apply the formula: V_drop = (2 x 100 x 20 x 10.37) / 6,530
- Calculate numerator: 2 x 100 x 20 x 10.37 = 41,480
- Divide: 41,480 / 6,530 = 6.35 V
- Calculate percentage: (6.35 / 120) x 100 = 5.29%
At 5.29%, this exceeds the NEC-recommended 3% maximum. You should upgrade to 10 AWG wire (10,380 CM), which would reduce the drop to about 3.99V (3.33%), or consider shortening the run. Using 8 AWG (16,510 CM) would further reduce it to 2.51V (2.09%).
Sources
- National Institute of Standards and Technology (NIST) — SI Units: nist.gov
- Khan Academy — Electrical Circuits: khanacademy.org
- Physics NIST — Metric (SI) Program: physics.nist.gov
Disclaimer: This calculator is for informational and educational purposes only. Results are estimates and may not reflect exact values.
Last updated: November 3, 2026