Skip to content
Embed

Paste this on your site. The attribution link is required and is what makes embedding free.

Voltage Drop Calculator — Free Online Electrical Tool

Calculate voltage drop across electrical conductors based on wire gauge, length, current draw, and material to ensure your installation meets NEC recommendations.

A
ft

Voltage Drop Results

6.35 V

5.29% drop

Supply Voltage

120.0 V

Receiving End

113.65 V

Formula

V_drop = (2 x L x I x R) / CM

L = 100 ft, I = 20 A, Gauge = 12 AWG (copper)

Warning: 5.29% exceeds the NEC recommended 3% maximum. Consider using a larger wire gauge or shorter run.

Wire Gauge Reference Table

AWG Gauge Circular Mils Max Amps (Cu) Max 3% Run @120V/20A (Cu) Typical Use
14 AWG 4,107 15A 30 ft 15A lighting circuits
12 AWG 6,530 20A 47 ft 20A general purpose
10 AWG 10,380 30A 75 ft 30A dryers, water heaters
8 AWG 16,510 40A 119 ft 40A ranges, large appliances
6 AWG 26,240 55A 189 ft Sub-panels, large equipment
4 AWG 41,740 70A 301 ft Feeder circuits, sub-panels
2 AWG 66,360 95A 479 ft Service entrance, large feeders
1/0 AWG 105,600 125A 762 ft Main service entrance

Related Calculators

About this calculator

Voltage Drop Formula

Single-Phase Voltage Drop

V_drop = (2 x L x I x R) / CM

Percentage Voltage Drop

%V_drop = (V_drop / V_supply) x 100

Three-Phase Voltage Drop

V_drop = (1.732 x L x I x R) / CM

Variables Explained

  • V_drop: The voltage lost across the wire conductors, measured in volts. This is the difference between the supply voltage at the panel and the voltage delivered to the load at the far end of the circuit.
  • L: One-way wire length in feet. The factor of 2 in the formula accounts for both the supply conductor and the return conductor, since current must flow through both.
  • I: Current flowing through the circuit in amperes. Higher current produces proportionally more voltage drop because the power lost as heat in the conductor equals I-squared times R.
  • R: Resistivity of the conductor material in ohm-circular mils per foot. Copper has a resistivity of 10.37 and aluminum has 17.02 at 75 degrees Celsius, the standard operating temperature assumed by the NEC.
  • CM: Circular mil area of the wire gauge. This is the cross-sectional area of the conductor; larger values mean less resistance and less voltage drop per unit length.

Step-by-Step Example

Calculate the voltage drop for a 20A load on a 120V circuit using 12 AWG copper wire with a 100-foot run:

  1. Identify values: L = 100 ft, I = 20 A, R = 10.37 (copper), CM = 6,530 (12 AWG)
  2. Apply the formula: V_drop = (2 x 100 x 20 x 10.37) / 6,530
  3. Calculate numerator: 2 x 100 x 20 x 10.37 = 41,480
  4. Divide: 41,480 / 6,530 = 6.35 V
  5. Calculate percentage: (6.35 / 120) x 100 = 5.29%

At 5.29%, this exceeds the NEC-recommended 3% maximum. You should upgrade to 10 AWG wire (10,380 CM), which would reduce the drop to about 3.99V (3.33%), or consider shortening the run. Using 8 AWG (16,510 CM) would further reduce it to 2.51V (2.09%).

Sources

Disclaimer: This calculator is for informational and educational purposes only. Results are estimates and may not reflect exact values.

Last updated: November 3, 2026